Fatek B1 Series PLC: Italian Programming Manual
Condividi
Installation Guide: Fatek B1 Series PLC
Everything you need to know to start programming the Fatek B1 Series micro PLC. Discover compatible software and basic instructions. Click on the module image for more info.
🛠 Mechanical Mounting
- Ultra-compact (slim) structure with the ability to expand hardware on the right side via a dedicated flat bus
- Rear quick-mounting on a standard 35 mm DIN rail using spring-loaded locking clips
- In environments with continuous vibration, it is mandatory to pull out the integrated slotted plastic hooks on the bottom and mount to the panel using M4 screws
- Additional modules can only be connected on the right side; lock both ends on the DIN rail using metal end clamps
- Clearance: at least 50 mm above and below the housing
- Smart side-by-side feature: continuous side-by-side installation with no side gaps when using dedicated expansion modules
💻 Software Configuration
- Software: WinProladder (official Fatek Automation portal)
- Interface: Front Port 0 (4-pin mini-DIN), Fatek FB-U2C-MDIN21 cable (USB-mini-DIN)
- Drivers: Prolific or FTDI depending on the cable chip
- Connection: PLC > Connection Setup, standard parameters: 9600 bps, 7 data bits, even parity, 1 stop bit
- Limitation: The B1 series does not support online editing; the PLC must be in stop mode to transfer changes
- Reading from PLC: File > Open PLC, save as .pld file
- Quick cloning: Connect a new empty CPU of the same model, open the .pld file, and launch PLC > Write (less than 5 seconds)
- Online monitoring: Press F2 to enter monitor mode; active rungs will be highlighted in green
⚡ Safety and Wiring
- Always disconnect main power before working on screw terminals
- Transistor outputs (MJ or MT): maximum switchable current per point is 0.5A
- Install flyback diodes (e.g., 1N4007) in parallel with every external DC inductive load
📝 Extra Notes
Limit: maximum 64 total I/O points (native + expansions). Analog expansions use Port 1; additional serial communications go to Port 2. No hardware retention (latch) on Y0-Y255 outputs. Addresses: X0-X63/Y0-Y63, M0-M1999 volatile, M2000-M7999 retentive.